Cables to Go 29509 Manuale Utente

Navigare online o scaricare Manuale Utente per Switch di rete Cables to Go 29509. G-Schedule Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 14
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
Remark
unit cost Total cost of
supply
Unit cost Total cost of
ETC
1
2
3
4
5
6
7
8
10
A
11KV OVERHEAD LINE WORK (NEW LINE/AUGMENTATION)
1 CONDUCTING ROUTE SURVEY , TRIMMING OF TREE BRANCHES ALONG THE ROAD AS PER APPROVED ROUTE MAP
AND PEGGING OF ROUTE WITH SECTION POINT/DOUBLE POLE LOCATION FOR SPECIFIED NUMBERS OF DIFFERENT
WORKS AT DIFFERENT LOCATIONS.
KM 81 0.00 0 197.70 16013.70
2 SUPPLY & ERECTION OF 12.8 MTR. LONG LATTICE TOWER MADE OF 65 X 65 X 5 MM M.S. ANGLE WITH 50 X 6 MM
M.S. FLAT FOR BRACING INCLUDING EXCAVATION OF PIT 1.50 X 1.50 X 2.10 M IN GROUND. THE TOWER SHOULD
BE ERECTED BY CC GROUTING & MUFFED IN CEMENT CONCRETE OF MIX RATIO 1:3:6 HAVING SIZE OF 1.20 X 1.20
X 2.10 M OVER BASE CONCRETE OF 100 MM THICK IN MIX 1:5:10 AS PER IS SPECIFICATIONS. THE REMAINING
POSITION OF THE PIT BE BACK FILLED WITH WATERING & RAMMING AND SURPLUS MATERIAL SHALL BE DISPOSE-
OFF WITHIN LEAD OF 50 M.
a.
IN ALL TYPES OF SOIL - TOWER WEIGHT - 508 KG
Nos.
25
25421.15
1392.15
34803.75
b.
ORDINARY ROCK (WHERE BLASTING IS NOT REQUIRED) / PACCA ROAD -TOWER WEIGHT 508 KG.
Nos.
0
25421.15
0
2234.87
0.00
c.
HARD ROCK/CC ROAD -TOWER WEIGHT 508 KG.
Nos.
0
25421.15
0
3140.60
0.00
3 SUPPLY & ERECTION OF 116X100 RS JOIST 11.8 Mtr. long INCLUDING EXCAVATION OF PIT 1.50 X 1.50 X 2.10 M
IN GROUND. THE RS JOIST SHOULD BE ERECTED BY CC GROUTING & MUFFED IN CEMENT CONCRETE OF MIX
RATIO 1:3:6 HAVING SIZE OF 1.20 X 1.20 X 2.10 M OVER BASE CONCRETE OF 100 MM THICK IN MIX 1:5:10 AS
PER IS SPECIFICATIONS. THE REMAINING POSITION OF THE PIT BE BACK FILLED WITH WATERING & RAMMING
AND SURPLUS MATERIAL SHALL BE DISPOSE- OFF WITHIN LEAD OF 50 M. (Approx weight-250 kg)
a.
IN ALL TYPES OF SOIL
Nos.
0
9212.25
0
397.60
0.00
b.
ORDINARY ROCK (WHERE BLASTING IS NOT REQUIRED) / PACCA ROAD -Approx.WEIGHT -250 KG.
Nos.
0
9212.25
0
501.86
0.00
SCHEDULE - P("G Schedule")
SCHEDULE OF PRICES FOR SUPPLY, ERECTION, TESTING AND COMMISSIONING OF 33KV,11 KV-LT LINE/UG CABLE/DT SUBSTATIONS AND ASSOCIATED SUB-SYSTEMS AT DIFFERENT LOCATIONS OF
SAWAI MADHOPUR CITY. (TN-191)
S.N. Particulars
Unit
Tent. Qty. Cost of Design,
manufacture & supply of
material including all taxes
& duties (In Rs.)
Cost of Erection ,testing ,
commissioning alongwith
associated civil works
including all taxes& duties
(In Rs.)
b.
ORDINARY ROCK (WHERE BLASTING IS NOT REQUIRED) / PACCA ROAD -Approx.WEIGHT -250 KG.
Nos.
0
9212.25
0
501.86
0.00
c.
HARD ROCK/CC ROAD -Approx.WEIGHT -250 KG.
Nos.
0
9212.25
0
888.26
0.00
d. PROVINDING AND LAYING CEMENT CONCRETE INCLUDING COMPACTION ETC. AS PER SPECIFICATION DETAILED
ABOVE
cum 120 0.00 0 1913.21 229585.20
4 SUPPLY & ERECTION OF 9.00 M PCC POLES (400 KG) IN ALLIGNMENT INCLDUING EXCAVATION OF PIT IN GROUND
AND BACK FILLING OF SOIL CONSOLIDATING EACH DEPOSIT LAYER OF 0.15 MTR. BY PROPER WATERING &
RAMMING ETC. IN THE LENGTH.
a.
IN ALL TYPES OF SOIL.
Nos.
11
2218.06
24398.66
463.26
5095.86
b.
ORDINARY ROCK (WHERE BLASTING IS NOT REQUIRED) / PACCA ROAD.
Nos.
125
2218.06
277257.5
573.51
71688.75
c.
HARD ROCK/CC ROAD.
Nos.
109
2218.06
1049.79
5 SUPPLY AND FIXING OF 11KV 'V' CROSS ARMS MADE OF ISA M.S.ANGLE 65 X 65 X 6 MM ON THE EXISTING POLE
COMPLETE WITH EARTHING ARRANGEMENT OF M.S.FLAT WELDED WITH CROSS ARMS INCLUDING ALL
NECESSARY CLAMPS OF M.S. FLAT 50 X 6 MM, NUT & BOLTS ETC. WEIGHT OF THE ITEM WILL BE AS PER
DRAWING EARTHING ARRANGEMENT WITH CLAMPS, NUT & BOLTS ETC.
Nos. 475 407.01 193329.75 21.74 10326.50
6 SUPPLY AND FIXING OF 11KV 'V' CROSS ARMS MADE OF M.S.CHANNEL 100 X 50 ISMC (9.56 KG. PER MTR.) ON
THE EXISTING LATTICE TOWER INCLUDING ALL NECESSARY EARTHING ARRANGEMENT WITH CLAMPS, NUT &
BOLTS ETC.
Nos. 0 649.32 0 21.74 0.00
7 SUPPLY & FIXING OF A SET OF 4 NOS. 11KV 'V' CROSS ARMS (CHAKRI) MADE ON M.S.CHANNEL 100 X 50 ISMC
(9.56 KG./M) WITH BRACING OF M.S.FLAT 50 X 10 MM INCLUDING ALL NECESSARY CLAMPS, NUT & BOLTS ETC. (
60 KG. APPROX.).
Nos. 0 1628.04 0 120.54 0.00
8 SUPPLY & FIXING OF M.S.CHANNEL 100 X 50 ISMC (FOR CUT POINT) 2 X 1.3 METER LONG WITH PILOT PATTI 50
X 6 MM THICK ON SINGLE SUPPORT/POLE/LATTICE STRUCTURE & NECESSARY CLAMPS, NUT & BOLTS ETC. (
29.5 KG. APPROX.).
Nos. 275 1432.66 393981.5 43.48 11957.00
9 SUPPLY & FIXING OF 11KV, 0.3 MTR. LONG TOP HAMPER MADE OF ISA M.S.ANGLE 65 X 65 X 6 MM ON THE
EXISTING POLE COMPLETE INCLUDING NUT & BOLTS ETC. (STEEL WT. 2.983 KG. APPROX.).
Nos. 425 142.75 60668.75 8.40 3570.00
10 SUPPLY & FIXING OF 11KV DOUBLE POLE LINE STRUCTURE SET FOR CUT POINT COMPLETE ON EXISTING POLES
IN ALL RESPECT WITH CLAMP, NUT & BOLTS AS REQURIED MADE FROM M.S.CHANNEL 100 X 50 X ISMC ( 9.56 KG.
PER MTR.) ISA M.S.ANGLE 65 X 65 X 6 MM, M.S.ANGLE 50 X 50 X 6 MM AND M.S.FLAT 50 X 6 MM ( 105 KG.
APPROX.)
Nos. 35 4478.22 156737.7 300.23 10508.05
11
SUPPLY & FIXING OF 11KV PORCELAIN PIN INSULATORS WITH PIN ON EXISTING POLE COMPLETE
Nos.
1980
90.21
178615.8
6.72
13305.60
12 SUPPLY & FIXING OF SET OF 2 NO. 11KV B&S TYPE 45 KN PORCELAIN DISC INSULATOR WITH 1 NO. HARDWARE
ON EXISTING BRACKET COMPLETE INCLUDING ALL ACCESSORIES ETC.
Set 610 896.09 546614.9 22.79 13901.90
13 SUPPLY & DRAWING OF OVERHEAD ACSR 100 SQ.MM. DOG CONDUCTOR ON EXISTING CROSS ARMS THROUGH
INSULATOR INCLUDING BINDING WITH 6 MM SOFT ALUMINIUM CONDUCTOR & TWISTING ETC. COMPLETE IN ALL
RESPECT. (COST OF MATERIAL INCLUDES THE SAG AND JUMPERING)
Km 10 52929.90 529299 1974.95 19749.50
Vedere la pagina 0
1 2 3 4 5 6 ... 13 14

Sommario

Pagina 1

Remarkunit cost Total cost ofsupplyUnit cost Total cost of ETC1234567810A 11KV OVERHEAD LINE WORK (NEW LINE/AUGMENTATION)1 CONDUCTING ROUTE SURVEY ,

Pagina 2

11 SUPPLY & LAYING OF EARTH MESH AT SUB-STATION AS PER APPROVED MAP & DESIGN USING MS FLAT 50 X 6MM & MS ROD 20 MM DIA INCLUDING LAYING OF

Pagina 3

24 SAFE LOADING AND UN-LOADING AND CARRIAGE OF 33/11 KV POWERTRANSFORMERS FROM SUB-STATION AND DEPOSIT IN STORES WITHIN 10 KMS. a.5.00 MVANOS.0.000010

Pagina 4

32.4 SUPPLY AND INSTALLATION OF VARIOUS EQUIPMENTS:SUPPLY AND ERECTION OF FOLLOWINGEQUIPMENTS COMPLETE WITH ACCESSORIES INCLUDING USE OF SPECIAL TOOL

Pagina 5

1 CONDUCTING ROUTE SURVEY , TRIMMING OF TREE BRANCHES ALONG THE ROAD AS PER APPROVED ROUTE MAPAND PEGGING OF ROUTE WITH SECTION POINT/DOUBLE POLE LOCA

Pagina 6

3 SUPPLY, FABRICATION AND FIXING OF BLACK CLAMP AND STAY CLAMP USING MS FLAT 50X10MM(COLD BENDING)FOR CROSS ARMS, STAY, EARTH AND GUARDING BRACKET OF

Pagina 7

SUPPLY & DRAWING OF OVERHEAD ACSR 100 SQ.MM. WEASEL CONDUCTOR ON EXISTING CROSS ARMSTHROUGH INSULATOR INCLUDING BINDING WITH 6 MM SOFT ALUMINIUM C

Pagina 8

14(i) SUPPLY & DRAWING OF OVERHEAD ACSR RABBIT CONDUCTOR ON EXISTING CROSS ARMS THROUGH INSULATORINCLUDING BINDING WITH 6 MM SOFT ALUMINIUM CONDUC

Pagina 9

3 PROVIDING ,FABRICATION AND FIXING OF BLACK CLAMP AND STAY CLAMP USING MS FLAT 50X10MM(COLDBENDING) FOR CROSS ARMS, STAY, EARTH AND GUARDING BRACKET

Pagina 10

4 SUPPLY AND ASSEMBLY, INSTALLATION & COMMISSIONING OF 11KV WITH ( 9 X 12KV POST INSULATOR) 400AMP. DOUBLE BREAK WITHOUT EB GO ISOLATOR SWITCH SET

Pagina 11

13(i) LOADING/TRANSPORATION FROM CIRCLE STORES, INSTALLATION, TESTING & COMMISSIONING OF 6.35/0.24 KVDISTRIBUTION TRANSFORMER ON ERECTED SUPPORT I

Pagina 12

10 SUPPLY AND ERECTION OF GS STAY WIRE OF SIZE 7/10 SWG TIGHTENED THROUGH 11KV STRAIN INSULATOR ONEXISTING STAY SET & POLE ETC., AS REQUIRED COMPL

Pagina 13

2 SUPPLY & INSTALLATION OF LT SUPPLY DISTRIBUTION BOX & CHANGE OVER FOR WITH STANDUNDERGROUNDSERVICE LINE AS PER SPECIFICATION OF NIGAM. EACH

Pagina 14

9COPPER CONDUCTORKm00.000347.430.0010AB CABLEKm100.0001848.9218489.2411PVC CABLE 4CX10 SQMMKm200.0002880.0057600.0012PVC CABLE 2CX4/6 SQMMKm1600.00019

Commenti su questo manuale

Nessun commento